Flow Analysis of Power in 150kv Transmission Line Using Gauss – Seidel in Substation Madura Region, App Surabaya
Pages: 58-62 Views: 3602 Downloads: 1317
Authors
[01] Efrita Arfah Zuliari, Electrical Engineering Department, Institut Teknologi Adhi Tama, Surabaya, Indonesia.
[02] Tri Mulyono, Electrical Engineering Department, Institut Teknologi Adhi Tama, Surabaya, Indonesia.
Abstract
In order to meet the needs of electric power in Madura 162.8 MW, it need an electrical power in the region Madura 162.8 MW hence the need for electric power is supplied from the plant - UJUNG (Indonesia Power) and also from GE Kenjeran of 115 MW and 63.8 MW. Therefore, the method used to analyze the amount of losses is by Gauss Seidel wherein the method is used to solve linear equations. Analysis of the results of the calculation, the value obtained by Gauss Seidel with total active power and reactive power on each bus to Madura is 162.8 MW 38.875 MVA. The value of losses in the transmission network of 4.796 MW and the total value for the voltage drop Madura 2.897%. As for the value voltage drop below the maximum value of ± 5%, or below the value of tolerance.
Keywords
Gauss-Seidel, Voltage Drop, Power Loss, Active and Reactive Powers
References
[01] Anna Guldbrand.2005. Analysis of an induction regulator for power flow control in electric power transmission systems, Masters Thesis, Department of Physics, Chemistry and Biology Linköpings universitet, SE-581 83 Linköping, Sweden.
[02] Goran Andersson. 2008. Modeling and Analysis of Electric Power Systems: Power Flow Analysis Fault Analysis Power Systems Dynamics and Stability, EEH - Power Systems Laboratory, ETH Zurich.
[03] Achmad Bambang Sumadiyana. 2009. Simulation power flow 150 kV system, region Jakarta – Banten by comparison grid systems and IBT, Under Graduate Thesis, Electrical EngineeringDepartment, Universitas Indonesia.
[04] Lucky Arie Wibowo. 2010. Modeling 150kV Indonesia Power System for Voltage Stability Studies, Master Thesis, Department of Electrical Sustainable Energy, Electrical Power System, Delft University of Technology.
[05] Afandi. 2011. Evaluation of power loss to 150 kV transmission line the feeder Kebonagung – Sengkaling, Seminar On Electrical, Informatics, And Its Education 2011, Electrical Engineering Department, Universitas Negeri.
[06] Wihartady H. 2009. Modeling of short circuit fault arc in 150 kV system and its influent on the performance of distance protection. Delft: TU Delft library.
[07] Anton Y. 2008. Power flow analysis the 150kV transmission network Lampung Province using Gauss Saidel Method, Universitas Jember.
[08] Kadir A. 2011. Electric power transmission (Revised Edition), UI-Press, University of Indonesia.
[09] Berahim H. 2011. Electrical power engineering basic, Graha Ilmu, Yogyakarta.
[10] Cekdin C. 2010. Electricity System (Example Problem and completion Using MATLAB), ANDI Offset, Yogyakarta.